Measurement of Infiltration Rate of Warm Air into Walk-in Coolers

Homayun K. Navaz, Kristina Kamensky, Ramin Faramarzi, Mazyar Amin

Research output: Contribution to conferencePresentation

Abstract

The tracer gas technique is used to experimentally measure the infiltration of warm air into walk-in coolers during its nominal operating conditions. The tracer gas samples captured before, during, and after the infiltration process are collected through sampling probes inside and outside the cooler. The infiltration rate can be calculated from this data. The transient nature of the infiltration rate that is captured in this approach signifies the shortcoming of the existing methodologies currently practiced in industry. It is found that the infiltration rate is a function of the temperature gradient between the inside and outside air, relative humidity, and the void volume in the cooler. It is also demonstrated that it is possible to derive a closed form equation based on the experimental data that can replace the current equations.

Original languageAmerican English
StatePublished - Jul 18 2012
Event9th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 2012 -
Duration: Jul 18 2012 → …

Conference

Conference9th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 2012
Period7/18/12 → …

Disciplines

  • Mechanical Engineering

Cite this